You are looking for information, articles, knowledge about the topic nail salons open on sunday near me dixell xr 72 ch pdf on Google, you do not find the information you need! Here are the best content compiled and compiled by the toplist.prairiehousefreeman.com team, along with other related topics such as: dixell xr 72 ch pdf dixell controller, dixell xr70cx, Dixell xr20ch manual, Dixell XR60CX manual, dixell xr70ch manual pdf, Emerson manual, Xr60, Emerson Climate Technologies
dixell xr 72 ch pdf
- Article author: webapps.emerson.com
- Reviews from users: 45701 Ratings
- Top rated: 3.7
- Lowest rated: 1
- Summary of article content: Articles about dixell xr 72 ch pdf Dixell Srl reserves the right to change the composition of its products, … Models XR70C and XR72C, 32×74 mm format, and XR70D, … …
- Most searched keywords: Whether you are looking for dixell xr 72 ch pdf Dixell Srl reserves the right to change the composition of its products, … Models XR70C and XR72C, 32×74 mm format, and XR70D, …
- Table of Contents:
DIXELL XR72CX CONTROLLER INSTALLING AND OPERATING INSTRUCTIONS | ManualsLib
- Article author: www.manualslib.com
- Reviews from users: 31591 Ratings
- Top rated: 3.6
- Lowest rated: 1
- Summary of article content: Articles about DIXELL XR72CX CONTROLLER INSTALLING AND OPERATING INSTRUCTIONS | ManualsLib View and Download dixell XR72CX installing and operating instructions online. Digital controller with defrost and fans management. XR72CX controller pdf … …
- Most searched keywords: Whether you are looking for DIXELL XR72CX CONTROLLER INSTALLING AND OPERATING INSTRUCTIONS | ManualsLib View and Download dixell XR72CX installing and operating instructions online. Digital controller with defrost and fans management. XR72CX controller pdf … View and Download dixell XR72CX installing and operating instructions online. Digital controller with defrost and fans management. XR72CX controller pdf manual download.dixell XR72CX manual, XR72CX instruction manuals, dixell user manuals, service manual, XR72CX pdf download, user guides, Controller
- Table of Contents:
dixell xr 72 ch pdf
- Article author: dixell.cz
- Reviews from users: 33674 Ratings
- Top rated: 4.0
- Lowest rated: 1
- Summary of article content: Articles about dixell xr 72 ch pdf XR70CXXR71CX – XR72CX. XR75CX-XR77CX. Controller for milk cooling and for air dryers. XR80CX. XR 10D XR20D. Thermostat and “off cycle” defrost controller. …
- Most searched keywords: Whether you are looking for dixell xr 72 ch pdf XR70CXXR71CX – XR72CX. XR75CX-XR77CX. Controller for milk cooling and for air dryers. XR80CX. XR 10D XR20D. Thermostat and “off cycle” defrost controller.
- Table of Contents:
dixell xr 72 ch pdf
- Article author: www.grupodisco.com
- Reviews from users: 26564 Ratings
- Top rated: 4.3
- Lowest rated: 1
- Summary of article content: Articles about dixell xr 72 ch pdf red compatible ModBUS-RTU tal como las unades de monitoreo Dixell de la familia X-WEB y permite programar el controlador a través del … …
- Most searched keywords: Whether you are looking for dixell xr 72 ch pdf red compatible ModBUS-RTU tal como las unades de monitoreo Dixell de la familia X-WEB y permite programar el controlador a través del …
- Table of Contents:
dixell xr 72 ch pdf
- Article author: www.gev-online.com
- Reviews from users: 17645 Ratings
- Top rated: 3.7
- Lowest rated: 1
- Summary of article content: Articles about dixell xr 72 ch pdf de supervision compatible ModBUS-RTU tel que les systèmes Dixell de la famille X-WEB. Elle permet également de programmer la liste des paramètres avec la … …
- Most searched keywords: Whether you are looking for dixell xr 72 ch pdf de supervision compatible ModBUS-RTU tel que les systèmes Dixell de la famille X-WEB. Elle permet également de programmer la liste des paramètres avec la …
- Table of Contents:
dixell xr 72 ch pdf
- Article author: www.kahancontrols.com
- Reviews from users: 28214 Ratings
- Top rated: 3.4
- Lowest rated: 1
- Summary of article content: Articles about dixell xr 72 ch pdf The icons of alarm and critical temperature are flashing. X—0. 0. XR. 77. 5C. 7.2 EXIT. …
- Most searched keywords: Whether you are looking for dixell xr 72 ch pdf The icons of alarm and critical temperature are flashing. X—0. 0. XR. 77. 5C. 7.2 EXIT.
- Table of Contents:
dixell xr 72 ch pdf
- Article author: dixellasia.com
- Reviews from users: 38593 Ratings
- Top rated: 4.6
- Lowest rated: 1
- Summary of article content: Articles about dixell xr 72 ch pdf Dixell srl reserves the right to amend this manual without prior notice. … be activated with the system fully configured and is described in the chapter. …
- Most searched keywords: Whether you are looking for dixell xr 72 ch pdf Dixell srl reserves the right to amend this manual without prior notice. … be activated with the system fully configured and is described in the chapter.
- Table of Contents:
See more articles in the same category here: 995+ tips for you.
DIXELL XR72CX CONTROLLER INSTALLING AND OPERATING INSTRUCTIONS
Digital controller with defrost and fans management
XR72CX
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be
used as a safety device.
Check the application limits before proceeding.
Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the
same and unchanged functionality.
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see
address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each
other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XR72CX, format 32 x 74 mm, is microprocessor based controller, suitable for applications on
medium or low temperature ventilated refrigerating units. It has four relay outputs to control
compressor 1, compressor 2, fan and defrost, which can be either electrical or reverse cycle (hot
gas). It is also provided with up to four NTC or PTC probe inputs, the first one for temperature
control, the second one, to be located onto the evaporator, to control the defrost termination
temperature and to managed the fan. The digital input can operate as third temperature probe. The
fourth one, to connect to the HOT KEY terminals is used to signal the condenser temperature alarm
or to display a temperature.
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a
network line ModBUS-RTU compatible such as the Dixell monitoring units of X-WEB family. It
allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed
through the keyboard.
3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according
to the temperature measured by the
thermostat probe with a positive
differential from the set point: if the
temperature increases and reaches set
point plus differential the compressor is
started and then turned off when the
temperature reaches the set point value
again.
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters “COn” and “COF”.
3.2 2
COMPRESSOR MANAGEMENT – XR72C ONLY
ND
The relay of the second compressor is activated in parallel with the relay of the first compressor, with
a possible delay set in the AC1 parameter. Both the compressors are switched off at the same time.
3.3 DEFROST
Two defrost modes are available through the “tdF” parameter: defrost through electrical heater (tdF
= EL) and hot gas defrost (tdF = in). Other parameters are used to control the interval between
defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or controlled by the
evaporator’s probe (P2P).
At the end of defrost dripping time is started, its length is set in the FSt parameter. With FSt =0 the
dripping time is disabled.
3.4 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the “FnC” parameter:
FnC = C_n: fans will switch ON and OFF with the compressor and not run during defrost;
FnC = o_n fans will run even if the compressor is off, and not run during defrost;
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter.
FnC = C_Y fans will switch ON and OFF with the compressor and run during defrost;
FnC = o_Y fans will run continuously also during defrost
An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe,
above which the fans are always OFF. This is used to make sure circulation of air only if his
temperature is lower than set in “FSt”.
3.4.1 Forced activation of fans
This function managed by the Fct parameter is designed to avoid short cycles of fans, that could
happen when the controller is switched on or after a defrost, when the room air warms the
evaporator. Functioning: if the difference of temperature between the evaporator and the room
probes is more than the value of the Fct parameter, the fans are switched on. With Fct=0 the function
is disabled.
1592020080 XR72CX GB m&M r1.1 27.03.2015
Temper.
SET
Compr.
ON
3.4.2 Cyclical activation of the fans with compressor off.
When Fnc = c-n or c-Y (fans in parallel to the compressor), by means of the Fon and FoF
parameters the fans can carry out on and off cycles even if the compressor is switched off. When the
compressor is stopped the fans go on working for the Fon time. With Fon =0 the fans remain always
off, when the compressor is off.
4. FRONT PANEL COMMANDS
: To display target set point; in programming mode it selects a parameter or confirm an
operation.
(DEF) To start a manual defrost
(UP): To see the max. stored temperature; in programming mode it browses the parameter
codes or increases the displayed value.
(DOWN) To see the min stored temperature; in programming mode it browses the parameter
codes or decreases the displayed value.
To switch the instrument off, if onF = oFF.
Not used.
KEY COMBINATIONS:
+
+
+
4.1 USE OF LEDS
Each LED function is described in the following table.
LED
MODE
ON
Compressor enabled
Flashing Anti-short cycle delay enabled
ON
Defrost enabled
Flashing Drip time in progress
ON
Fans enabled
Flashing Fans delay after defrost in progress.
ON
An alarm is occurring
ON
Continuous cycle is running
Time
ON
Energy saving enabled
°C/°F ON
Measurement unit
°C/°F Flashing Programming phase
5. MAX & MIN TEMPERATURE MEMORIZATION
5.1 HOW TO SEE THE MIN TEMPERATURE
1.
Press and release the n key.
2.
The “Lo” message will be displayed followed by the minimum temperature recorded.
3.
By pressing the n key again or by waiting 5s the normal display will be restored.
5.2 HOW TO SEE THE MAX TEMPERATURE
1.
Press and release the o key.
2.
The “Hi” message will be displayed followed by the maximum temperature recorded.
3.
By pressing the o key again or by waiting 5s the normal display will be restored.
5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
1.
Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt
message will be displayed)
2.
To confirm the operation the “rSt” message starts blinking and the normal temperature will be
displayed.
6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
display the probe value again.
6.2 HOW TO CHANGE THE SETPOINT
1.
Push the SET key for more than 2 seconds to change the Set point value;
2.
The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
To change the Set value push the o or n arrows within 10s.
3.
4.
To memorise the new set point value push the SET key again or wait 10s.
XR72CX
To lock & unlock the keyboard.
To enter in programming mode.
To return to the room temperature display.
FUNCTION
1.
Push and immediately release the SET key: the display will show the
Set point value;
2.
Push and immediately release the SET key or wait for 5 seconds to
1/4
So you have finished reading the dixell xr 72 ch pdf topic article, if you find this article useful, please share it. Thank you very much. See more: dixell controller, dixell xr70cx, Dixell xr20ch manual, Dixell XR60CX manual, dixell xr70ch manual pdf, Emerson manual, Xr60, Emerson Climate Technologies